Turn on the cooling water system. Here is an overview of the cooling
system which really is a heat exchanger using the central cooling medium
at KTH campus.
Inside of the left door is the mains switch to turn on. Here it is
shown in the ON-position. To the right is the standby switch which should
be turned from the "0" (zero) position to the
"AUT" position.
Above the standby switch (to the left
in the image below) is a temperature readout for six different
temperature sensors. They can be selected for readout with the
"+" and "-" buttons.
The sensors are positioned like this:
- 0: not connected
- 1: return water for circuit 1, cooling RIE stage, should be ~20°
- 2: return water for circuit 2, cooling RIE turbo pump, should be ~20°
- 3: return water for circuit 3, not used
- 4: return water for circuit 4, not used
- 5: return of KTH campus coolant, should be ~19°
- 6: input of KTH campus coolant, should be ~16°
In the center is the programmable regulator for temperature and
pressure (pump speed), to the right is a fault indicator panel.
At the lower right is a meter for the pressure inside the closed secondary
cooling loop going to the RIE.
The pressure MUST be between 1.5 bars
and 2.5 bars. If it is not; do not start the system,
call the lab-manager.