Some parameters have been changed to increase temperature
stability. Previous values in parenthesis.
These changes were made on 20171117 for the Ebeam lab and 20180103
for the Depo lab.
Manual page 68:
step compressor 1
compressor 1 dead zone 0.7°C (1°C)
compressor 1 differential 0.5°C (0.7°C)
Maual page 69:
low temperature limit
(stop dehumidification)
stop dehumidification dead zone 0.8°C (1.8°C)
stop dehumidification differential 0.8°C (0.6°C)
high temperature limit
(stop dehumidification)
stop dehumidification dead zone 0.7°C (1.2°C)
stop dehumidification differential 0.9°C (0.6°C)
Manual for Pegasus MP2000 with notes of parameter changes