Water chiller must start after power fail

The controller for the pump motor in the water chiller (heat exchanger) is default set to not start after a power loss. This is very bad, since there will be no cooling of the systems connected to the chiller after a power loss, but most systems automatically starts after a power loss.

Manual for pump motor controller

The pump motor controller have to be re-programmed to change this behaviour.

  1. Open the water chiller doors
  2. On the inside of the right hand door is a box containing the pump motor controller
  3. The box is opened with a special key or a large screw driver.
  4. Here is a picture of the control panel of the controller
  5. And here is a schematic of how to change the parameter n47 to value 2 (was 0). This will set the controller to "Autostart after power fail".
    Follow the green line from top to bottom and out the the right.

A. Liljeborg, 2020-06-29